Usage  and  application  scope
BY1  series  surge  protective  device  (protector  in  short)  is  applied  in  A.C  50/60  Hz  ,  ≤380V  in  the  following  electric  power  system  ,  such  as  TT  ,  IT  ,TN-S  ,  TN-C  and  TN-C-S  which  protects  the  electric  net  shocked  by  the  thunder  or  surge  over  voltage  .
Tripping  device
There's  tripping  device  designed  on  the  modular  of  the  protector.  When  the  protector  is  over  heat  or  shocked,  the  tripping  device  can  automatically  separate  it  from  the  electric  net,  at  the  same  time  showing  the  indication  signal.  It's  green  when  the  protector  is  normal,  red  when  tripping.
Alarm
The  power  of  the  alarm  is  supplied  by  AC220V.  In  normal  condition  it  is  green  and  the  opening  contact  is  closed  but  the  closing  contact  is  open.  It  is  with  the  function  of  alarming  and  showing:  the  alarm  will  sound  and  the  green  indicator  lamp  will  change  to  red  when  the  mould  of  the  protective  device  is  out  of  working.  And  the  alarm  will  not  stop  until  the  operator  pushes  the  stop  press  (but  the  red  lamp  is  still  showing).  If  the  trouble  can  not  be  dealt  within  24  hours,  the  alarm  will  sound  again.
Remote  signaling  contact
The  products  can  be  produced  available  with  the  accessory  of  remote  signaling  contact  which  is  an  opening  contact.  If  one  of  the  product's  mould  is  out  of  working,  the  contact  will  be  closed  and  send  the  trouble  information.  The  rated  data  of  the  remote  signaling  contact  is  AC36V,  1A.
 
Principal  parameters

1.  Maximum  continuous  operating  voltage                                                                              Uc~140  275  320  385  420  550V
2.  Test  classification                                                                                                                  II  grade  
3.  Protection  level                                                                                                                      Up  <  0.8  1.2  1.5  1.8  2.0  2.5kV
4.  Max.  discharging  current  (8/20µs)                                                                                       Imax  10  40  60kA
5.  Nominal  discharge  current  (8/20µs)                                                                                     In  5  15  20  30kA
 
Technical  Parameters

 
BY1-D/  -140-55 BY1-D/  -275- BY1-D/  -320-5 BY1-D/  -385-5 BY1-D/  -420-5 BY1-B/  -320-30 BY1-B/  -385-30
Maximum  continuous  operating  voltage  Uc
140  V 275  V 320  V 385  V 420  V 320V 385V
Voltage  protection  level  Up  <
0.8  kV 1.0  kV 1.5  kV 2.0  kV 2.0  kV 2.0kV 2.5kA
Nominal  discharge  current  In(8/20µs)  kA
5 5 5 5 5 30 30
Maximum  discharge  current  Imax  (8/20µs)  kA
10 10 10 10 10 60 60
Response  time  ns
<25
Width  mm
18
Color
Yellow Orange
Protection  level
IP20
Shell  material
Reinforced  fire-retardant  nylon  PBT
Fuse  Or  Switch  (A)
10  ---  16A
Connect  ways
L  ,N
2.5  ---  35  mm2 
Earthing  
4.0  ---  35  mm2               
Signal  line  
1.5mm2             
 
BY1-C/
BY1-C/
BY1-C/ BY1-C/ BY1-C/ BY1-C/    
140-15
-295
-340 -405 -440 -570    
Maximum  continuous  operating  voltage  Uc
140V 275V 320V 385V 420V 550V
Voltage  protection  level  Up  <
0.8kV 1.2kV 1.5kV 2.5kV 2.5kV2 .5kV
Nominal  discharge  current  In(8/20µs)  kA
15 20 20 20 20 20
Maximum  discharge  current  Imax  (8/20µs)  kA
40 40 40 40 40 40
Response  time  ns
<25
Width  mm
18
Color
grey
Protection  level
IP20
Shell  material
enforce  anti-  flame  PBT
Fuse  Or  Switch  (A)
25-32A
Connect  ways
L  ,N
2.5-35  mm2 
Earthing  
4.0  ---45  mm2             
Signal  line  
1.5mm2             
 
The  installation  position  and  application  of  BY-D
1.  Installed  on  the  joint  of  LPZ1  or  LPZ2  and  LPZ3.  

2.  Applied  in  household  distribution  boards,  computer  equipment,  information  equipment,  electronic  equipment  and  in  the  socket  box  in  front  of  control  equipment  or  near  the  control  equipment.
The  installation  position  and  application  of  BY-C
1.  C  grade  lightning  current  SPD  protection,  used  for  electric  connection  when  being  shocked.
2.  Installed  on  the  joint  of  LPZOB  or  LPZ1  and  LPZ2.  
3.  Generally  it's  installed  in  the  floor  distribution  board,  computer  center,  telcommunication  room,  elevator  control  room,  cable  TV  room,  floor  automatic  control  room,  guard  supervising  room,  fire  protection  center,  industrial  automatic  control  room,  frequency  conversion  equipment  control  room,  hospital  operating  room,  supervising  room  and  the  distribution  board  with  electronical  medical  equipment,  also  can  be  installed  in  the  whole  distribution  board  under  the  six  floors  household.  To  the  individual  building,  the  SPD  should  be  installed  in  the  distribution  board  of  every  household.  
The  main  structure  and  operating  principle
In  three-  phase  four-  line  system,  three  phase  lines  and  one  zero  line  are  connected  protective  device  to  the  earth  cable.  (figure  1  )  .  In  normal  situation,  the  protective  device  is  high  resistance,  when  the  over  voltage  brings  for  electric  network  shocked  by  thunder  or  other  reasons,  the  protective  device  will  rapidly  transmit  in  ns  ,  then  lead  the  voltage  into  earth  and  protect  the  electric  equipment.  As  the  surge  voltage  through  the  protective  device  and  after  disappear  it  will  recover  to  high  resistance  and  not  influence  the  normal  operating.  Figure  2  is  the  electric  principle  about  it.  
 
Installation:
 
It  adopts  35  mm  DIN  rail
It  is  linked  by  2.5  --  35  mm2  copper  wire  ,  and  there  are  2  wiring  methods:
1. From  power  switch  to  protective  device  ,  then  from  protective  device  again  to  the  load  end  .  This  way  suits  to  the  distribution  case  which  load  current  is  under  100  A  .  The  wire  section  should  be  selected  by  the  load  current  .
2. From  the  power  switch  to  protective  device  ,  also  from  the  power  switch  to  load  end  .  This  way  suits  to  the  distribution  case  which  load  current  is  over  100  A  .  The  wire  section  should  not  be  selected  by  the  load  current  ,  but  it  can't  be  longer  than  500  mm.  
 
The  earth  cable  should  choose  the  double  color  wire  which  is  over  4  mm2  but  not  longer  than  500  mm  .In  order  to  guarantee  electrical  network's  normal  operating  after  protective  device  losing  efficiency  ,  the  protective  device  which  linked  to  the  phase  line  must  be  connected  a  32A  fuse  box  
 
Adjustment,  operation,  maintenance  
 
1. There's  no  need  to  adjust  the  protector  after  installation.
2. The  protector  can  automatically  protect  the  electric  net  should  it's  installed  rightly.  
3.  When  operating,  check  whether  the  modular  scutcheon  is  red,  at  the  same  time  check  whether  the  indication  red  light  is  lighting,  then  can  change  the  malfunction  device.  
 
 
 
 

 

 